10KV Cold Shrinkalbe Silicone Rubber Pre-moulded Rear Plug

If you are interested in this product, you can sendmsg
Product Name: 10KV Cold Shrinkalbe Silicone Rubber Pre-moulded Rear Plug
Product Type: 10KV Cold Shrinkalbe
Exhibitors: SEEFAR
Product Documentation: No Related Documents

Brief

This termination kits are shielded bolted connector, can provide a quick disconnect feature for cable and equipments on power distridution systems. It can work under water surely.


10KV Cold Shrinkalbe Silicone Rubber Pre-moulded Rear Plug  A detailed description of

8. 7/15kV Prefabricated cold shrinkable separable termination kits

 

Material: silicone rubber
Voltage: 8. 7/15kV
Suitable cable range: 25-400 mm2 cross-linked cable

 

This termination kits are shielded bolted connector, can provide a quick disconnect feature for cable and equipments on power distridution systems. It can work under water surely.

 

Application:
It can be applied to O-net Switchgear, branch box transformer substation etc.
WHB 10-630 Series also named fore-connector kits, can be connected to switchgear directly.
WHBK 10-630 Series also named sub-connector kits, can be applied to connecting with WHB 10-630 Series, to form double joint type or 3-joint type.

 
 
Technical Data

Items

Standard Requirements

Test Result

Remarks

  AC
  withstand
  45kV, 1min no flashover no
  breakdown

  45kV, 1min, no breakdown and flashover
  occurred

  OK
  Partial 
  discharge
  test
  13kV, ≤10pC
PhaseyellowGreenRed
pC≤3pC≤3pC≤3pC
  OK
  Impulse
  voltage
  withstand

  105kV, at 10 positive and 10
  negative impulses, no
  flashover no breakdown

  105kV, no flashover and breakdown
  occurred
  OK
  DC 
  withstand
  52kV, 15min no flashover no
  breakdown
  52kV, 15min no flashover no breakdown
  occurred
  OK
  Thermal
  short-
  circuit
  (conductor)
  20kA, 2s, no transfigure and    welding on all parts

  20kA, 2s, no transfigure and welding
  occurred on all parts

  OK

  Dynamic
  short-
  circuit

  50kA, 0. 3s, no 
  transfigure and
  welding on all parts
  50kA, 0. 3s, no transfigure and welding on all parts  OK

 

Specification

Part NO.

Insulation OD
for cable core

Cable cross section

Rated current

Remarks

 

(mm)

(mm2)

(A)

 
  WHB-630/25-50  15-18  25-50  630  Fore-connector kits
  WHB-630/70-120  19-22. 5  70-120  630
  WHB-630/150-240  23. 5-28. 5  120-240  630
  WHB-630/300-400  29. 5-35  300-400  630
  WHB-630/25-50  15-18  25-50  630  Sub-connector kits
  WHB-630/70-120  19-22. 5  70-120  630
  WHB-630/150-240  23. 5-28. 5  120-240  630
  WHB-630/300-400  29. 5-35  300-400  630
Leave a message for product
Title
Contact
Tel
Content
Verify Code
Click to change
Note:1. Shortcut key for send message :Alt+s or Ctrl+Enter!
2. If necessary, please leave your detail contact!