Product List

10KV Cold Shrinkable Joint

If you are interested in this product, you can sendmsg
Product Name: 10KV Cold Shrinkable Joint
Product Type: Cold Shrinkable Joint
Exhibitors: SEEFAR
Product Documentation: No Related Documents

Brief

10KV Cold Shrinkable Joint have 2 kinds of voltage grades: 10KV and 35KV, respective applicable voltage range: 8.7~15KV; 26~35KV


10KV Cold Shrinkable Joint  A detailed description of

10KV Cold Shrinkable  Joint

Product Detail:

Introduction:
1. Have 2 kinds of voltage grades: 10KV and 35KV, respective applicable voltage range: 8.7~15KV; 26~35KV
2. Can be used as 1-core and 3-core
3. Can be used for indoor, outdoor and joint.
4. Sold by set, with the material in the set, it can be installed easily.
 
Properties:
1. Reliable insulation: the kit is made of imported liquid silicone rubber which has excellent characters of elasticity and insulation.
2. Simply Installation:
   All the kits are Pre-moulded in factory: anyone unskilled can easily complete the installation. Needs no fire, save time.
3. Widely Application: Anti-dirtiness, aging-resistant, waterproof, excellent cold and heat-resistant character, suitable for high altitude, cold, dankish, salt fog and heavy polluted areas. Special suit for the petroleum, chemical plants and mine.
4. Advance equipment: The imported equipments have high automatism and reliable properties.
5. Excellent Appearance: with longer cold shrinkable tube, no commissural line. And smooth surface.

 

Sample

Items

Standard

Test Result

Note

10kv indoor outdoor
termination
and middle
joint          

Frequency
voltage

45kv,1min
no flashover no breakdown

45kv,1min no flashover,no breakdown under dankish condition     

Passed

Local discharge test

13kv,≤20pc

Phase

Yellow

Green

red

Passed

Pc

≤2Pc 

≤2Pc

≤2Pc

Burthen circle test,3 Periods

5h heat,3h cooling,conductor
temperature
95 during heating

pass through 3 circle,conductor temperature 90-95℃

Assess according
to following
test

Local pressure test

13kv,discharge
20pc

Phase

Yellow

Green 

Red 

Passed

Pc

≤2Pc 

≤2Pc

≤2Pc

Impact pressure test

105kv,15min,
10times allow flashover once,but dont count into total number

105kv no flashover,no 
breakdown

Passed

Cathode D.C.test

52kv,15min no flashover,no 
breakdown

52kv,15min no flashover,no 
breakdown

Passed

4h frequency voltage test

35kv,4h, no flashover,no breakdown

35kv,4h, no flashover,no breakdown

Passed

Leave a message for product
Title
Contact
Tel
Content
Verify Code
Click to change
Note:1. Shortcut key for send message :Alt+s or Ctrl+Enter!
2. If necessary, please leave your detail contact!